Features
- Small size, simple installation and easy operation
- IP65 waterproof grade
- Built in resolution 16-bit AD
LED:
- Input 4-20mA, accuracy 0.1%
- Units: Kpa, Mpa, Bar
LCD:
- Input 4-20mA/0-10V, accuracy 0.1%
- Units : Kpa, Mpa, Bar, Pa, mBar, Psi, ℃, ℉, kg/cm2, atm,mmhg, mH2O, m, cm, mm, V, mV, A, mA
Applications
- Display pressure value(LED)
- Display pressure, temperature, length, current or voltage values, etc(LCD)
Specifications
LED:
Display: 4-digit LED display
Internal resolution: 16-bit AD
Signal output: 4-20mA or 1-channel NPN output
Ambient temperature: -20~70℃
Temp. Drift: <50ppm
Voltage drops: <3.5VDC
Sampling rate: 4 times/second
Protection circuit: Power supply polarity-reverse wiring protection
Over-current protection: Limited 30mA
LCD:
Display: LCD with backlight (white or green backlight)
Display bytes: -1999~19999
Internal resolution: 16-bit AD
Signal output: 2-wire 4-20mA or 3-wire 0-10V
Ambient temperature: -20~70℃
Temp. Drift: <50ppm
Voltage drops: <3.5VDC
Sampling rate: 4 times/second
Protection circuit: Power supply polarity-reverse wiring protection
Over-current protection: Limited 30mA
Product Dimensions
Menu Description
LED:
1) After power on, press the S key first, then press the up key to enter the setting password;
2) Up key to modify numbers, down key to shift;
3) Customer mode menu password: 0006;
*Notes:
1) Please wire correctly according to the wiring method corresponding to the output signal of the product;
2) The current output meter is connected in series with the transmitter. If the transmitter is not connected after power-on, the terminals 1 and 2 at the bottom of the meter need to be short-circuited.
LCD:
1) After power on, press the S key first, then press the up key to enter the setting password;
2) Up key to modify numbers, down key to shift;
3) Customer mode menu password: 00006;
*Notes:
1) -1.0 means the range sign is negative; 1.0 means the range sign is positive;
2) The parameter can compensate the deviation between the displayed value and the
actual value. For example, the displayed value is 10.05, and the zero point correction is set to -0.05, then the displayed value after compensation is 10.00.
Installation & Tips
1. Prevent the sensor from contacting with corrosive or overheated media, and prevent dross from depositing in the conduit;
2. When measuring liquid pressure, the pressure tap should be opened on the side of the process pipeline to avoid sedimentation and accumulation of slag;
3. When measuring gas pressure, the pressure tap should be opened at the top of the process pipeline, and the transmitter should also be installed on the upper part of the process pipeline, so that the accumulated liquid can be easily injected into the process pipeline;
4. The pressure guiding pipe should be installed in a place with small temperature fluctuations;
5. When measuring steam or other high-temperature media, it is necessary to connect a condenser such as a buffer pipe (coil), and the working temperature of the sensor should not exceed the limit;
6. When freezing occurs in winter, anti-freezing measures must be taken for the transmitter installed outdoors to prevent the liquid in the pressure port from expanding due to freezing and causing damage to the sensor;
7. When measuring the liquid pressure, the installation position of the transmitter should avoid the impact of the liquid (water hammer phenomenon), so as to avoid the sensor from being damaged by over pressure;
8. Do not touch the diaphragm with hard objects on the sensor probe, as it will damage the diaphragm;
9. When wiring, ensure that the pins are defined, and no short circuit occurs, which may easily lead to circuit damage;
10. Do not use a voltage higher than 36V on the sensor, which may easily cause damage. (The 5-12V specification cannot have an instantaneous voltage higher than 16V)
11. Make sure that the electrical plug is installed in place. Pass the cable through the waterproof joint or flexible tube and tighten the sealing nut to prevent rainwater from leaking into the transmitter housing through the cable.
12. When measuring steam or other high-temperature media, in order to connect the transmitter and the pipe together, a heat dissipation pipe should be used, and the pressure on the pipe should be used to transmit to the sensor. When the measured medium is water vapor, an appropriate amount of water should be injected into the cooling pipe to prevent the superheated steam from directly contacting the transmitter and causing damage to the sensor.
13. In the process of pressure transmission, some points should be paid attention to: there should be no air leakage at the connection between the transmitter and the cooling pipe; be careful when opening the valve, so as not to directly impact the measured medium and damage the sensor diaphragm; the pipeline must be kept unblocked, Prevent deposits in the pipe from popping out and damaging the sensor diaphragm.